Product

ETC2800

Details

O2 PROBE – SUPPLY VOLTAGE: 115/230 VAC 15% – POWER CONSUMPTION: 65VA – SUPPLY FREQUENCY: 50/60 HZ 5% – OPERATING TEMPERATURE RANGE: 0 TO 60ºC – CONTROL UNIT PROTECTION CATEGORY: IP20 OR IP65 – CONTROL UNIT DIMENSIONS – IP20: 196 X 287.67 MM – CONTROL UNIT DIMENSIONS – IP65: 200 X 280 MM – CONTROL UNIT WEIGHT: 3 KG – DISPLAY TYPE (OPTIONAL): DOT MATRIX OF 40 CHARACTERS – MAXIMUM NUMBER OF FUELS: 2 – AUXILIARY ANALOG INPUTS: 0 – 5V (1MA MAX.) / 4 – 20MA (SWITCH SELECTED) – MODULATION INPUT: 0 – 5V (1MA MAX.) / 4 – 20MA (SWITCH SELECTED) – BURNER ON/OFF AND FUEL SELECTION INPUTS: 115/230VAC 1.5MA MAX. – ALARM OUTPUTS: 2 X MONOPOLAR SWITCHING – CONTACT RATING: 2A @ 250VAC RMS. – NUMBER OF 4-20MA CURRENT OUTPUTS: 4 (ISOLATED) – MAXIMUM LOOP RESISTANCE: 750 OHMS – ISOLATION VOLTAGE: 50V – RS485: 2 – WIRE (INSULATED) WITH GROUND, TERMINATION RESISTOR SELECTED USING A LINK. SPECIFIC PROTOCOL ETC. SEE HA221471 (ETC SERIAL COMMUNICATION PROTOCOL MANUALS) FOR DETAILS – INSULATION VOLTAGE: 50V – INTERFACE FOR OXYGEN PROBE: ETC SPECIFIC – INPUT TEMPERATURE INPUT: 2 WIRES R.T.D. STACK TEMPERATURE INPUT: TYPE K THERMOCOUPLE – TEST GAS SOLENOID OUTPUT: 150MA (MAX) 50V MAXIMUM SUPPLY VOLTAGE – CALIBRATION GAS SOLENOID OUTPUT: 150MA (MAX) @ 30VAC – MAXIMUM DISTANCE BETWEEN PROBE AND O CONTROL UNIT

Contact us to receive this part's quotation.

We connect your company to the main manufacturers worldwide, reducing costs and delivery terms. Contact us to learn more!

Manufacturer

SKU

Product family

Product model

Price

Availability