INDUSTRIAL POWER SUPPLY WITH 12VDC/100W BATTERY CHARGER FOR MOUNTING ON DIN RAIL.
– INPUT BETWEEN 96 AND 240 VAC AND FREQUENCY BETWEEN 47 AND 63 HZ
– MAIN OUTPUT: ADJUSTABLE BETWEEN 12VDC AND 15 VDC / RIPPLE MAXIMUM 120
MVP-P / MINIMUM CURRENT 4.5 A
– BATTERY OUTPUT: ADJUSTABLE BETWEEN 12 AND 15 VDC / RIPPLE 120MVP-P
MAXIMUM / MINIMUM CURRENT 2.5 A
– TYPICAL EFFICIENCY 87% / WORKING TEMPERATURE BETWEEN -30 TO +70 °C /
WORKING HUMIDITY BETWEEN 20 TO 90% RH NON-CONDENSING
– OVERLOAD PROTECTION TYPE HICCUP WITH AUTOMATIC RECOVERY WHEN
THE FAULT IS CLEARED FROM A 105% OVERLOAD
– OVERVOLTAGE PROTECTION THAT OPERATES WITH A MAXIMUM 124% OFF TYPE AND
AUTOMATIC RECOVERY WHEN THE FAULT IS CLEARED
– BATTERY PROTECTION THAT CUTS OFF SUPPLY WHEN THE BATTERY OUTPUT LEVEL IS
LESS THAN 10 VDC
– COMPLIES WITH UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 60950.1 SAFETY STANDARDS – EMC IMMUNITY COMPLIANCE: BS EN/EN61000-4-2,3,4,5,6,8,11,BS EN/EN55035,BS EN/EN61204-3, EAC TP TC 020, COMPLIES WITH BS EN/EN54-4 FOR FIRE DETECTION AND ALARM SYSTEMS.
– MTBF 1820.4K HRS MIN. TELCORDIA SR-332 (BELLCORE) ; 410.1K HRS MIN.
MIL-HDBK-217F (25?)