RIPTION UNITS DATA
AIR FLOW NOMINAL FLOW M³/H 18,000/ EFFECTIVE FLOW M³/H 17,847
COOLING CAPACITY MEASURED FOR MADRID CONDITIONS ACCORDING TO UNE 100.001-085, CONSIDERING THE EFFECTIVE FLOW, WATTS, 19,652
ENERGY CONSUMPTION (MAX) WATTS 1,200/(MIN) WATTS 360 (AVERAGE AVERAGE SPEEDS) % 30 % LOWER
MAXIMUM TOTAL CURRENT OF THE AIR CONDITIONER (FOR CABLE DIMENSIONS / CIRCUIT BREAKER) AMP 8
FAN DIAMETER MM 610/ SPEED (MAX.) RPM 1,390/ TOTAL PRESSURE PA 160
MOTOR POWER (MAX / MIN) WATTS 1,100 / 60 TO 200- 264V / TYPE AXIAL- INVERTER / RANGE OF VARIABLE SPEED RPM 170-1390/ VOLTAGE/PHASE/HZ (INPUT) V /- / HZ 220/ 1 / 50-60
WATER PUMP SYNCHRONOUS MOTOR/ POWER (INPUT) WATTS 30/ FLOW RATE LITERS / MINUTE 23/ VOLTAGE / PHASE / HZ V /- / HZ 220 / 1 /50
FILTER NUMBER OF FILTERS UD 4/ FILTER SIZE MM 825X620X100/ MAXIMUM AIR SPEED M/SEC 1.36/ SATURATION EFFICIENCY % 89.1
TANK CAPACITY LITERS 25
WATER RESERVOIR INLET INCHES 1/2” MALE BSP/ DRAIN MM 50 MALE BSP/ MAX NOISE LEVEL DB <70
DIMENSIONS DIMENSIONS (LENGTH X WIDTH X HEIGHT) MM 1,110 X 1,110 X 950 (A)/ VOLUME M³ 1.26/ SHIPPING DIMENSIONS (LENGTH X WIDTH X HEIGHT) MM 1110 X 1110 X 1020/ SHIPPING WEIGHT KG 77/ EMPTY WEIGHT KG 67/ OPERATING WEIGHT KG 92/ OUTLET DUCT DIMENSIONS MM 660X660.
WATER CLEANING / DISINFECTION SYSTEM AUTOMA