NAME 8-POINT DC INPUT UNIT WITH TERMINAL BLOCK
MODEL CJ1W-ID201
RATED INPUT VOLTAGE 12 TO 24 VDC
RATED INPUT VOLTAGE RANGE 10.2 TO 26.4 VDC
INPUT IMPEDANCE 2.4 KΩ
INPUT CURRENT 10 MA TYPICAL (AT 24 VDC)
ON VOLTAGE/ON CURRENT 8.8 VDC MIN./3 MA MIN.
OFF VOLTAGE/OFF CURRENT 3 VDC MAX./1 MA MAX.
ON RESPONSE TIME 8.0 MS MAX. (CAN BE SET TO BETWEEN 0 AND 32 MS IN THE SETUP.) *1
OFF RESPONSE TIME 8.0 MS MAX. (CAN BE SET TO BETWEEN 0 AND 32 MS IN THE SETUP.) *1
NUMBER OF CIRCUITS 8 INDEPENDENT CIRCUITS
NUMBER OF SIMULTANEOUSLY
ON POINTS 100% SIMULTANEOUSLY ON
INSULATION RESISTANCE 20 MΩ MIN. BETWEEN EXTERNAL TERMINALS AND THE GR TERMINAL (100 VDC)
DIELECTRIC STRENGTH 1,000 VAC BETWEEN THE EXTERNAL TERMINALS AND THE GR TERMINAL FOR 1 MINUTE AT A LEAKAGE CURRENT OF
10 MA MAX.
INTERNAL CURRENT CONSUMPTION 80 MA MAX.
WEIGHT 110 G MAX.