SWITCH; MODIFIER: AUTOMATIC; MANUFACTURER NAME: SCHNEIDER ELECTRIC; PART NUMBER: C16F4TM080; ADDITIONAL CHARACTERISTICS: COMPACT NSX160F TMD80, ELECTRICAL SPECIFICATIONS: RATED CURRENT (IN): 80 A (40°C), OPERATING VOLTAGE (UE): 690VAC 50/60HZ, NUMBER OF POLES: 4 POLES (4P) WITH 4 PROTECTED POLES (4D), NEUTRAL POSITION: LEFT, BREAKING CAPACITY (ICU): 36KA (380/415VAC), RATED INSULATION VOLTAGE (UI): 800VAC, RATED IMPULSE WITHSTAND VOLTAGE (UIMP): 8KV, 85KA (220/240VAC), 8 KA (660/690VAC), PROTECTION AND CONTROL UNIT: CONTROL UNIT: TM-D (THERMAL-MAGNETIC), PROTECTION FUNCTIONS: LI (LONG TIME AND INSTANTANEOUS PROTECTION), THERMAL SETTING (IR): ADJUSTABLE FROM 0.7 TO 1 X IN (56-80A), MAGNETIC SETTING (LI): FIXED AT 640A, NEUTRAL PROTECTION: 1 X IR (FULL PROTECTION), INSTALLATION AND DIMENSIONS: MOUNTING MODE: FIXED, ON BACKPLATE, MOUNTING POSITION: HORIZONTAL OR VERTICAL, PHYSICAL DIMENSIONS: 140MM (WIDTH) X 161MM (HEIGHT) X 86MM (DEPTH), WEIGHT: 2.6KG, DURABILITY: 40,000 MECHANICAL CYCLES AND UP TO 20,000 ELECTRICAL CYCLES AT 440V IN, STANDARDS AND ENVIRONMENT: REGULATIONS: EN/IEC 60947-2 AND UL 60947-4-1, PROTECTION RATINGS: IP40 (FRONT) AND IK07, WORKING TEMPERATURE: -25 TO 70°C, SUSTAINABILITY: TOTAL CARBON FOOTPRINT OF 152KG CO2 EQ, DESIGNED TO BE RECYCLABLE AND PVC-FREE